ContaminationSensor CS 1000 Reading the analog output
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 67/112
BeWa CS1000 3764916 300 en-us 2012-08-29.doc 2012-08-29
HDA.ISO – Analog signal ISO to HDA 5500
The HDA.ISO signal consists of 6 measured values (START / ISO 4 / ISO 6 / ISO 14
/ ISO 21 / Status) which are output sequentially. Synchronization with the
downstream control unit is a prerequisite.
The signal output is as follows:
Time Measured variable Signal duration
in s
Current/Voltage
Start signal 0 -- 2 20 mA / 10 V
Pause 2 4 mA / 2 V
Signal 1 ISO 4 2 Current / Voltage for signal
Pause 2 4 mA / 2 V
Signal 2 ISO 6 2 Current / Voltage for signal
Pause 2 4 mA / 2 V
Signal 3 ISO 14 2 Current / Voltage for signal
Pause 2 4 mA / 2 V
Signal 4 ISO 21 2 Current / Voltage for signal
Pause 2 4 mA / 2 V
Signal 5 Status 2 Current / Voltage for signal
Pause 30 4 mA / 2 V
Zobrazit stránku 66